Basic Info.
Model NO.
KC-SVG
Rated Input Line Voltage
400/600V
Power Grid Frequency
50/60 Hz
Transport Package
Wooden Box
Specification
mounting type
Trademark
KC
Origin
China
HS Code
8537109090
Production Capacity
30000PCS/Month
Product Description
Static Var Generator KCSVG
KCSVG is a dynamic reactive power compensation device that utilizes a self-converting power semiconductor bridge converter. KCSVG is currently the best solution in the field of reactive power control. Compared with the traditional regulator, capacitor reactor, thyristor control reactor TCR as the main representative of the traditional SVG and other methods.
Model Description:

Working Principle:
The basic principle is that the self-commutated bridge circuit is directly connected in parallel to the power grid through the reactor, and the phase of the output voltage of the bridge current exchange side is appropriately adjusted or the AC current is directly controlled to make the KCSVG inductive or capacitive on the grid side, so as to enable the circuit to absorb or emit the reactive current that meets the requirements, and to realize the purpose of dynamic reactive power compensation.

Specification :
System parameters | ||
Rated input line voltage | 400/480/690V | |
Input phase voltage range | -20%~+15% | |
Power grid frequency | 50Hz/60Hz ( range: ±10%) | |
Parallel operation | Unlimited | |
Overall efficiency | ≥98% | |
Power grid structure | 3P3L/3P4L | |
CT | 150/5 ~ 10,000/5 | |
Performance indicators | ||
compensation capacity | 25/35/50/60/100kvar | |
Response time | <1ms | |
Target power factor | Adjustable from -1 to +1 | |
Cooling mode | Smart air cooling: 220L/sec | Smart air cooling: 405L/sec |
Noise level per module | <65dB | |
Communications and monitoring capabilities | ||
Communications ports | RS485, CAN, and network port | |
Communications protocols | Modbus and PMBus | |
Alarm | Available | |
Monitoring | Monitoring module, and optional centralized monitoring modules | |
Environment requirement | ||
Altitude | 1500 m. Between 1500 m to 4000 m, according to GB/T3859.2, the power decreases by 1% for every additional 100 m. | |
Operating temperature | -10ºC ~ 40ºC | |
Relative humidity | 5%~ 95%, non-condensing | |
Protection class | IP20 (other IP classes arecustomizable.) | IP20 |