Product instruction:
The working principle of the IGY SVG series static vargenerator is to connect a voltage-type inverter in parallel tothe power grid through a filter.By adjusting the amplitudeand phase of the AC side output voltage of the inverter,it candynamically control the reactive power in the power gridsystem for accurate compensation,the instantaneous response time is less than 50us,and the full response time isless than 10ms,avoiding overcompensation and undercompensation.It is currently the best solution in thefield of reactive power compensation.
220V series | 380V series | 500V series | 690V series | |
Altitude | <2000m,above 2000m,derate according to GB/T3859.2 | |||
ambient temperature | -20~+50ºC | |||
Relative humidity | ≤90%,no condensation on the surface when the monthly minimum temperature is 25ºC | |||
pollution leye | Level III below | |||
Operating Voltage | AC220V±20% | AC380V±20% | AC500V±20% | AC690V±20% |
working frequency | 50Hz±5% | |||
Rated compensation capacity | 5kvar | 15/35/50/75/100kvar | 90kvar | 120kyar |
Grid structure | L/N | 3P3W/3P4W | ||
Number of units connected in paralle | Ulimited | |||
Overall machine efficiency | ≥97% | |||
On-off frequency | 32kHz | 16kHz | 12.8kHz | 12.8kHz |
Function selection | Reactive power | Reactive power,Reactive power+imbalance | ||
Reactive power compensation rate | ≥99% | >95% | ||
full response time | <10ms | |||
noise | ≤60dB | ≤60dB | ≤65dB | ≤65dB |
control method | 2-way RS485 interface (supports GPRS/WIFI) | |||
Protection | Overload,software/hardware overcurrent,grid overvoltage and undervoltage,power failure overtemperature,frequency abnormality protection,etc | Overload,software/hardware overcurrent,grid overvoltage and undervoltage,grid voltage imbalance,power failure,overtemperature,frequency abnormality,short circuit protection,etc | ||
Installation method | Rack/wall-mounted | Rack | ||
Incoming line | Back incoming(rack type), upper incoming(wall-mounted) | Back incoming line | ||
Protection level | IP20 |