Basic Info.
Model NO.
Century Star Series
Protection
Over Load/ Current/Voltage, Short Circuit
Application
Computers, Data Rooms, Communications, Servers
Classification
Lighting/Power
Standby Time
Standard Machine
Standby UPS
Sine Wave Output UPS
Output Capacity
Medium Type
Equipment Mode
Both
Brand
Upsen
Weight
10~300kgs
Transport Package
Carton/Pallet
Specification
CE & ISO Certificate
Trademark
UPSEN
Origin
China
HS Code
8504402000
Production Capacity
50, 000PCS/Month
Product Description
UPSEN Products Quick View
1: Mini DC UPS 18W, 30W, 60W, 100W
2: Line Interactive UPS 400Va-3000Va
3: Online UPS 1Kva-800Kva (High Frequency & Low Frequency Model)
Modular UPS Power 10K-500Kva
Outdoor UPS specially designed for outside telecom use 1K-100Kva
4: Power& Solar Inverter 300W- 200KVA
5: MPPT Solar Charge Controller 10-100Amp
6: Portable UPS Power Generator 300W - 1000W
7: Accessories: UPS&Solar Battery, Battery Cabinet, SNMP Card, AS400,
High Frequency Online UPS Century Star Series 1K-10Kva (1ph in/1ph out) with PF1 Output
Key Features:
- Ture Double-Conversion
- Microprocessor Control Optimized Reliability
- Output Power Factor PF 1
- Settable Charger Current from 1A - 12A Through LCD Screen
- Configurable Battery Voltage
- Input Power Factor Correction
- Wide Input Voltage(110V - 300V)
- Converter Mode Available
- Generator Compatible
- EPO for 6 - 10KVA Model
- Communication Port SNMP Slot, RS232, USB etc.
- Techcanil Specification
Model C1K C1KL C2K C2KL C3K C3KL C6K C6KL C10K C10KL Redundancy Parallelled & Redundancy Rated Capacity 1KVA 2KVA 3KVA 6KVA 10KVA INPUT Input Formats L + N + PE Nominal Voltage 208 / 220 / 230 / 240VAC Input Voltage Range 110 ~ 300VAC Frequency Range 44 ~ 56Hz or 54Hz ~ 66Hz Power Factor ≥0.99 Harmonic Distortion ≤3%THD(Linear Load); ≤5% THD(Non-linear Load) OUTPUT Output Formats L + N + PE Output Voltage 208 / 220 / 230 / 240VAC Voltage Regulation ±1% Frequency Range Line Mode: Synchronized Range, Battery Mode: 50 / 60Hz ±0.1% Harmonic Distortion ≤2%THD(Linear Load); ≤5% THD(Non-linear Load) ≤2%THD(Linear Load); ≤4% THD(Non-linear Load) Power Factor 0.9 / 1 1 Transfer Time AC Mode to Battery Mode 0ms, Inverter Mode to Bypass Mode 4ms Overlord Capacity Line Mode:
1min@105%~125% load
30s@125%~150% load
0.5ms@>150% loadLine Mode:
30min@102%~105% load
10min@105%~125% load
30s@125%~150% Load
500ms@>150% loadLine Mode:
10min@102%~105% load
10min@105%~125% load
10s@125%~150% Load
500ms@>150% loadEFFICIENCY AC Mode Peak Efficiency 93% Peak Efficiency 94% Peak Efficiency 95% Full Loader Efficiency 90% Full Loader Efficiency 91% Full Loader Efficiency 95% BATTERY Numbers 7Ah*2(3) 7Ah*4(6) 7Ah*6(8) 7Ah*16(20) 16~20pcs 7Ah*16(20) 16~20pcs Typical Recharge Time depending on user needs Charging Current 1A(Default)
1~12A(Settable)
External Battery Pack1~12A
(Settable)1A(Default)
1~12A(Settable)
External Battery Pack1~12A
(Settable)1A(Default)
1~12A(Settable)
External Battery Pack1~12A
(Settable)1A(Default)
1~12A(Settable)
External Battery Pack1~12A
(Settable)1A(Default)
1~12A(Settable)
External Battery Pack1~12A
(Settable)ENVIRONMENT Ambient Temperature 0 ~ 40ºC Humidity 20% ~ 95%(No Condensing) Storage Temperature -15 ~ 60ºC(Battery: 0 ~ 40ºC) Altitude The altitude should not exceed 1000m, and the height above 1000m should bereduced to a maxinmun of 4000m. Rafer to IEC62040 INDICATORS LCD Load Level, Battery Level, AC Mode, Battery Mode, Bypass Mode, So On CERTIFICATION Certification PHYSICAL Unit Dimension(MM) 350*145*230 410*190*325 410*190*325 500*248*616 500*240*460 500*248*616 500*240*460 Net Weight(KG) 18.6 9 19 10 25 11 57 18 68.5 20 MANAGEMENT Interface RS232, Intelling Slot Selectable *Product Specifications are Subject to Change Without Notice.
High Frequency Online UPS Queen Star Series 10K-80KVA (3ph in/3ph out)Key Features:
- True double-conversion.
- DSP technology guarantees high performance.
- Output power factor 0.8.
- Active power factor correction in all phases.
- 50Hz/60Hz frequency converter mode.
- Accepts dual-mains inputs.
- Generator compatible.
- SNMP+USB+RS-232 multiple communications.
- 3-stage extendable charging design for optimized battery performance.
- Adjustable battery numbers.
- Maintenance bypass available.
- Optional N+X parallel redundancy.
Technical Specification: | |||||||
Index | 33Q 10KL | 33Q 20KL | 33Q 30KL | 33Q 40KL | 33Q 60KL | 33Q 80KL | Comments |
Input | |||||||
Input voltage | |||||||
Rated voltage | 380V / 400V / 415Vac | ||||||
Phase | three phase with ground | ||||||
Turn on voltage range | 380V: (207±9~475±9) VAC | ||||||
Bypass voltage range | 380V: (105±9~518±9)VAC | Could be adjusted by software. | |||||
Input frequency | |||||||
Rated frequency | 50Hz | 60Hz can configure through LCD | |||||
Frequency low loss | (40~49) ±0.2Hz(default:46Hz) | Could be adjusted by software. | |||||
Frequency high loss | (51~60)±0.2Hz(default:54Hz) | ||||||
Input power factor | |||||||
Input power factor | > 0.99 | full R load | |||||
Generator | Support generator input | Generator rating≥2*UPS rating | |||||
Input current | |||||||
Rated current | 14A | 28A | 42A | 67A | 91A | 121A | |
Input THDI | <10% | ||||||
Output protection | |||||||
Rating protection | 32A Breaker | 50A Breaker | 60A Breaker | 80A Breaker | 100A Breaker | 125A Breaker | |
Output power | |||||||
VA/watt | 10KVA/8KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | 60KVA/48KW | 80KVA/64KW | 0.9PF is optional |
Rated voltage | 380Vac | Sine Wave | |||||
Voltage range | 380V /400V /415Vac | Could be adjusted by software. 10% derating for 208VAC/220VAC | |||||
Voltage regulation | ±1% | ||||||
Voltage distortion | ≤5% | ≤10% | Full RCD load | ||||
≤3% | Full R load | ||||||
DC offset | ≤200mV | ||||||
Transient response | ≤9% | R load 0%~100%~0% | |||||
≤6% | R load 20%~100%~20% | ||||||
Transient recovery | ≤60ms voltage recovery to 90% | Full RCD load | |||||
Bypass output before turn-on | YES | ||||||
Crest ration | 3:1 | ||||||
Output frequency range | |||||||
Normal mode | 1: Same as input frequency(46Hz~54Hz) 2: 50Hz(Input frequency>54Hz or Input frequency<46Hz) | ||||||
Battery mode | (50±0.1) Hz | ||||||
Slew rate | 1 Hz/Sec | ||||||
Efficiency | |||||||
Normal mode | > 93% | > 90% | |||||
Battery mode | > 90% | > 90% | |||||
Overload | |||||||
Normal mode/battery mode | Overload warning only | 105%±5%≤load | |||||
1min,then transfer to bypass and alarm. | 105%±5%<load≤125%±5% | ||||||
30S, then transfer to bypass and alarm. | 125%±5%<load≤150%±5% | ||||||
300mS, then transfer to bypass and alarm. | load>150%±5% | ||||||
Automatically retransfer | YES | ||||||
Short protection | |||||||
Normal/ battery mode | YES | ||||||
Transfer time | |||||||
Normal to battery mode | 0mS | ||||||
Battery to normal mode | 0mS | ||||||
Battery and charger | |||||||
Battery | |||||||
Rated voltage | 192Vdc | ±192Vdc | ±192V/±216V/±240Vdc | ||||
Battery quantity | 16pcs | 32pcs | 32/36/40pcs | ||||
Charger | |||||||
Output voltage | (219.2±3)VDC | (277±3)VDC | (219.2±3)VDC | (277±3)VDC | (554±3)VDC | ||
Charge time | Depends on the external battery capacity | ||||||
Charge current | 7.5A | 6A | 5A | 4A | 15A(15-20A) | ||
Communication | |||||||
RS232 interface | YES | ||||||
Intelligent slot | YES | ||||||
Monitor software | Appending with UPS | ||||||
Display | |||||||
LCD Screen + LED Indicators | |||||||
Environment | |||||||
Work temperature | 0ºC~40ºC | ||||||
Altitude | <1000m | ||||||
Audible noise | ≤60dB | ||||||
Storage temperature | -15ºC~45ºC | ||||||
Work humidity | 20%~95% | ||||||
Outline dimension and net weight | |||||||
L*W*H (mm) | 710*260*717 | 700*300*960 | |||||
Net weight(Kg) | 45 | 50 | 58 | 60 | 100.5 | 104 |
UPSEN INTRODUCTION